dc.identifier.citation

Bebbington, D. (2020) ‘Combined Heating and Power: Control Documentation and Efficiency Measurement’, The Plymouth Student Scientist, 13(1), p. 112-142.

en_US
dc.identifier.urihttp://hdl.handle.net/10026.1/16508
dc.description.abstract

The University of Plymouth has an experimental Combined Heating and Power (CHP) plant with a poorly documented bespoke space heating loop (SHL), which has led to the existence of some controls with unknown purposes. This research seeks to produce complete documentation for the CHP through experimental methods. This includes taking visual inspections, Thermocouple (TC) temperature measurements, Transit Time Ultrasonic Flow Meter (TTUF) volumetric flow measurements, and Electronic Control Unit (ECL) temperature measurements. The overall thermal efficiency (ηth) measurement methodology will then be assessed as to whether or not it is a suitable protocol for compliance to EU Boiler Efficiency Directive 92/42EEC, and ISO17025: General requirements for the competence of testing and calibration laboratories. The CHP plant was successfully reverse engineered through experimentation to produce documentation of the controls in the form of a schematic. A labelling system was established creating reference between the actual CHP system, and the schematic. The efficiency of the CHP was determined using three different judgements of what is useful space heating. This was found to have a major contribution to the result. The values of ηth varied from 92.3% to 57.2% for assuming all heating power produce by the CHP is useful, to assuming that heat transfer in distribution is to not useful space. A protocol was established to closer meet the EU Directive, however complete compliance would prove challenging. Some areas of priority were highlighted to adhere closer to ISO17025, with certain calibrations and the tracing of systematic errors helping to closer meet the terms of the standard.

en_US
dc.language.isoenen_US
dc.publisherUniversity of Plymouthen_US
dc.rightsAttribution 3.0 United States*
dc.rights.urihttp://creativecommons.org/licenses/by/3.0/us/*
dc.subjectCombined heatingen_US
dc.subjectPoweren_US
dc.subjectControl Documentationen_US
dc.subjectEfficiency measurementen_US
dc.subjectengineeringen_US
dc.subjectTransit Time Ultrasonic Flow Meteren_US
dc.subjectvolumetric flow measurementsen_US
dc.subjectSpace Heatingen_US
dc.subjectEU Directive 92/42/EECen_US
dc.subjectISO17025en_US
dc.titleCombined Heating and Power: Control Documentation and Efficiency Measurementen_US
dc.typeArticleen_US
plymouth.issue1
plymouth.volume13
plymouth.journalThe Plymouth Student Scientist


Files in this item

Thumbnail
Thumbnail
Thumbnail
Thumbnail

This item appears in the following Collection(s)

Show simple item record

Attribution 3.0 United States
Except where otherwise noted, this item's license is described as Attribution 3.0 United States

All items in PEARL are protected by copyright law.
Author manuscripts deposited to comply with open access mandates are made available in accordance with publisher policies. Please cite only the published version using the details provided on the item record or document. In the absence of an open licence (e.g. Creative Commons), permissions for further reuse of content should be sought from the publisher or author.
Theme by 
Atmire NV